B10. Process Output Variable View-2&B11. Control Variable View-1

|||||
| ------------- |:-------------:| -----:|
|Minimum Value (最小值)| 绝对的最小可接受值。| - |R/W|
|Maximum Value(最大值)| 绝对的最大可接受值。| -| R/W|
|Minimum Deviation(最小偏差) |可接受的最小变化值。| - |R/W|
|Maximum Deviation(最大偏差)| 可接受的最大变化值。| -| R/W|
|Value Accepted(接受值)| TRUE:表示新的测量值已被SMOC接受和使用,因为它满足PV检查条件。 FALSE:表示由于PV检查条件不满足,SMOC未接受使用新测量值。 BAD:表示“尚未初始化”。| R| R|
|POV Estimation(POV估计值) |由不可测量干扰模型(观测器)计算的POV估计值。 这些值被用作控制器在故障(即,无效的坏条件等)情况下的替换测量值。 |R |R|
|POV Innovation(POV更新)| 实际测量值与预测值之间的差异。 |R| R|
|按钮||||
|APPLY Button (应用按钮)| 如前所述。 |R/W |R/W|
|UNDO Button(撤销按钮)| 在单击Apply(应用)按钮之前取消新输入的参数。然后上一个参数显示为黑色。| R/W| R/W|
(R:只读,R / W:读,写或执行, -:不显示)

B11被控变量视图

被控变量数据在所选控制器的所选CV视图上显示和输入。
Control Variable(被控变量)视图有“ENG”和“OPE”两种操作模式。 以下是ENG模式的HIS窗口。

查看

B10. Process Output Variable View-2&B11. Control Variable View-1_第1张图片
Figure B2.2.8.1 Items/Parameters under CV View 图B2.2.8.1 CV视图下的条目/参数

条目描述

需要由操作员和工程师输入的各个条目/参数如下。

| 条目 | 描述| 操作员模式 | 工程师模式|
| ------------- |:-------------:| -----:|
| Tag Name (位号名)| CV位号名 | R| R|
| Tag comment (位号描述)| CV的描述。| R| R|
| Remove From Control(从控制中移除)| 选择TRUE时,从控制和优化目标中删除CV; 选择FALSE时,在控制和优化目标中保持CV。 | R/W| R/W|
| Priority (优先级)| 可以根据控制要求将CV优先级定义为1到100的数。如果在实现稳态时存在控制问题,则CV通过分配的相应数值给予优先级次序。| R | R/W|
| * Set Value Type(设定值类型)| 指示CV的类型。 SETRNG表示区域控制,即CV将被控制在指定的限制(区域)内; SETPNT表示设定点控制,即CV将被控制在指定的设定点; LOLIMIT表示只有CV低限的区域控制。低限可以更改。高限也是; HILIMIT表示只有CV高限的区域控制。高限可以更改。| R| R|
| Setpoint Tracking Filter(设定点跟踪滤波)| 当SET VALUE TYPE在SETPNT(设定点)控制时,此条目有效。 TRUE表示SETRANGE HIGH / SET RANGE LOW将跟踪相应的CV值。 FALSE表示SETRANGE HIGH / SET RANGE LOW不跟踪相应的CV值。 | R | R/W|
| * Set Range High Limit(设置范围高限)| 定义了CV的高限目标值。| R/W| R/W|


原文:

|||||
| ------------- |:-------------:| -----:|
|Minimum Value | Absolute minimum acceptable value| - |R/W|
|Maximum Value |Absolute maximum acceptable value| - |R/W|
|Minimum Deviation| Minimum acceptable change in the value |-| R/W|
|Maximum Deviation| Maximum acceptable change in the value| -| R/W|
|Value Accepted |TRUE: Indicates whether new measurement has been accepted and used by SMOC as it satisfies the PV check conditions. FALSE: Indicates that new measurement of has not been accepted and not used by SMOC as it does not satisfies the PV check conditions. BAD: indicates ‘Not yet initialized’. |R| R|
|POV Estimation |Estimated value of POV computed by Unmeasured Disturbance Model (Observer) These values are used as replacement values for the measurement by the controller in case of failure i.e. invalid bad condition etc. |R| R|
|POV Innovation| Difference between the actual measurement and the prediction.| R| R|
|Button|
|APPLY Button | As Explained Earlier R/W| R/W |R/W|
|UNDO Button| Cancel a newly entered parameter before the “Apply” button is clicked. Then previous parameter is displayed in black.| R/W| R/W|
(R : Read Only, R/W : Read, Write or Execute, -:Not displayed)

B11. Control Variable View

Control Variable data are displayed and entered on the selected CV view of the selected controller.
Control Variable view has two operations such as “ENG” and “OPE” modes. Following are the HIS windows for the ENG modes.

View

Description of items

Various items/parameters need to be entered by operator and engineer is described below.

|Item | Description |Operator mode |Engineer mode|
| ------------- |:-------------:| -----:|
|Tag Name | CV Tag Name |R| R|
|Tag comment | CV’s Comments |R| R|
|Remove From Control| TRUE is selected to remove CV from Control and optimization Objectives. FALSE is selected to keep CV for Control and optimization Objectives. |R/W|R/W|
|Priority |CV’s Priority can be defined from 1 to 100 based on control requirement. If there is a control problem to achieve steady state then CV are given low priority by assigning numerical value accordingly. |R |R/W|
|* Set Value Type| The type of CV is indicated SETRNG indicates Zone Control i.e. CV will be controlled within specified limits (zone) SETPNT indicates set point Control i.e. CV will be controlled at specified set point. LOLIMIT indicates Zone Control with only low limit on CV. .Low limit can be changed. High limit is HILIMIT indicates Zone Control with only high limit on CV. High limit can be changed. |R |R|
|Setpoint Tracking Filter |This information is effective when SET VALUE TYPE is in SETPNT (Set point) control. TRUE indicates SETRANGE HIGH/SET RANGE LOW will track the Corresponding CV value. FALSE indicates SETRANGE HIGH/SET RANGE LOW Will not track the Corresponding CV value.| R |R/W|
|* Set Range High Limit |CV’s upper target value is defined. |R/W| R/W|